Rockwell Automation RSLinx Enterprise Software (LogReceiver.exe) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 does not handle input correctly and results in a logic error if it calculates an incorrect value for the “Total Record Size” field. By sending a datagram to the service over Port 4444/UDP with the “Record Data Size” field modified to a specifically oversized value, the service will calculate an undersized value for the “Total Record Size” that will cause an out-of-bounds read access violation that leads to a service crash. The service can be recovered with a manual reboot. The patches and details pertaining to these vulnerabilities can be found at the following Rockwell Automation Security Advisory link (login is required): https://rockwellautomation.custhelp.com/app/answers/detail/a_id/537599
The product performs a calculation that can produce an integer overflow or wraparound when the logic assumes that the resulting value will always be larger than the original value. This occurs when an integer value is incremented to a value that is too large to store in the associated representation. When this occurs, the value may become a very small or negative number.
The product reads data past the end, or before the beginning, of the intended buffer.
Link | Tags |
---|---|
https://ics-cert.us-cert.gov/advisories/ICSA-13-095-02 | third party advisory us government resource |