CVE-2018-11452

Description

A vulnerability has been identified in Firmware variant IEC 61850 for EN100 Ethernet module (All versions < V4.33), Firmware variant PROFINET IO for EN100 Ethernet module (All versions), Firmware variant Modbus TCP for EN100 Ethernet module (All versions), Firmware variant DNP3 TCP for EN100 Ethernet module (All versions), Firmware variant IEC104 for EN100 Ethernet module (All versions < V1.22). Specially crafted packets to port 102/tcp could cause a denial-of-service condition in the EN100 communication module if oscillographs are running. A manual restart is required to recover the EN100 module functionality. Successful exploitation requires an attacker with network access to send multiple packets to the EN100 module. As a precondition the IEC 61850-MMS communication needs to be activated on the affected EN100 modules. No user interaction or privileges are required to exploit the security vulnerability. The vulnerability could allow causing a Denial-of-Service condition of the network functionality of the device, compromising the availability of the system. At the time of advisory publication no public exploitation of this security vulnerability was known.

Category

7.5
CVSS
Severity: High
CVSS 3.0 •
CVSS 2.0 •
EPSS 0.40%
Vendor Advisory siemens.com Vendor Advisory siemens.com
Affected: Siemens AG Firmware variant IEC 61850 for EN100 Ethernet module
Affected: Siemens AG Firmware variant PROFINET IO for EN100 Ethernet module
Affected: Siemens AG Firmware variant Modbus TCP for EN100 Ethernet module
Affected: Siemens AG Firmware variant DNP3 TCP for EN100 Ethernet module
Affected: Siemens AG Firmware variant IEC104 for EN100 Ethernet module
Published at:
Updated at:

References

Frequently Asked Questions

What is the severity of CVE-2018-11452?
CVE-2018-11452 has been scored as a high severity vulnerability.
How to fix CVE-2018-11452?
To fix CVE-2018-11452, make sure you are using an up-to-date version of the affected component(s) by checking the vendor release notes. As for now, there are no other specific guidelines available.
Is CVE-2018-11452 being actively exploited in the wild?
As for now, there are no information to confirm that CVE-2018-11452 is being actively exploited. According to its EPSS score, there is a ~0% probability that this vulnerability will be exploited by malicious actors in the next 30 days.
What software or system is affected by CVE-2018-11452?
CVE-2018-11452 affects Siemens AG Firmware variant IEC 61850 for EN100 Ethernet module, Siemens AG Firmware variant PROFINET IO for EN100 Ethernet module, Siemens AG Firmware variant Modbus TCP for EN100 Ethernet module, Siemens AG Firmware variant DNP3 TCP for EN100 Ethernet module, Siemens AG Firmware variant IEC104 for EN100 Ethernet module.
This platform uses data from the NIST NVD, MITRE CVE, MITRE CWE, First.org and CISA KEV but is not endorsed or certified by these entities. CVE is a registred trademark of the MITRE Corporation and the authoritative source of CVE content is MITRE's CVE web site. CWE is a registred trademark of the MITRE Corporation and the authoritative source of CWE content is MITRE's CWE web site.