A vulnerability has been identified in Desigo PX automation controllers PXC00-E.D, PXC50-E.D, PXC100-E.D, PXC200-E.D with Desigo PX Web modules PXA40-W0, PXA40-W1, PXA40-W2 (All firmware versions < V6.00.320), Desigo PX automation controllers PXC00-U, PXC64-U, PXC128-U with Desigo PX Web modules PXA30-W0, PXA30-W1, PXA30-W2 (All firmware versions < V6.00.320), Desigo PX automation controllers PXC22.1-E.D, PXC36-E.D, PXC36.1-E.D with activated web server (All firmware versions < V6.00.320). The device contains a vulnerability that could allow an attacker to cause a denial of service condition on the device's web server by sending a specially crafted HTTP message to the web server port (tcp/80). The security vulnerability could be exploited by an attacker with network access to an affected device. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise the availability of the device's web service. While the device itself stays operational, the web server responds with HTTP status code 404 (Not found) to any further request. A reboot is required to recover the web interface. At the time of advisory publication no public exploitation of this security vulnerability was known.

Categories

5.3
CVSS
Severity: Medium
CVSS 3.1 •
CVSS 2.0 •
EPSS 0.59%
Vendor Advisory siemens.com
Affected: Siemens AG Desigo PX automation controllers PXC00-E.D, PXC50-E.D, PXC100-E.D, PXC200-E.D with Desigo PX Web modules PXA40-W0, PXA40-W1, PXA40-W2
Affected: Siemens AG Desigo PX automation controllers PXC00-U, PXC64-U, PXC128-U with Desigo PX Web modules PXA30-W0, PXA30-W1, PXA30-W2
Affected: Siemens AG Desigo PX automation controllers PXC22.1-E.D, PXC36-E.D, PXC36.1-E.D with activated web server
Published at:
Updated at:

References

Frequently Asked Questions

What is the severity of CVE-2019-13927?
CVE-2019-13927 has been scored as a medium severity vulnerability.
How to fix CVE-2019-13927?
To fix CVE-2019-13927, make sure you are using an up-to-date version of the affected component(s) by checking the vendor release notes. As for now, there are no other specific guidelines available.
Is CVE-2019-13927 being actively exploited in the wild?
As for now, there are no information to confirm that CVE-2019-13927 is being actively exploited. According to its EPSS score, there is a ~1% probability that this vulnerability will be exploited by malicious actors in the next 30 days.
What software or system is affected by CVE-2019-13927?
CVE-2019-13927 affects Siemens AG Desigo PX automation controllers PXC00-E.D, PXC50-E.D, PXC100-E.D, PXC200-E.D with Desigo PX Web modules PXA40-W0, PXA40-W1, PXA40-W2, Siemens AG Desigo PX automation controllers PXC00-U, PXC64-U, PXC128-U with Desigo PX Web modules PXA30-W0, PXA30-W1, PXA30-W2, Siemens AG Desigo PX automation controllers PXC22.1-E.D, PXC36-E.D, PXC36.1-E.D with activated web server.
This platform uses data from the NIST NVD, MITRE CVE, MITRE CWE, First.org and CISA KEV but is not endorsed or certified by these entities. CVE is a registred trademark of the MITRE Corporation and the authoritative source of CVE content is MITRE's CVE web site. CWE is a registred trademark of the MITRE Corporation and the authoritative source of CWE content is MITRE's CWE web site.