CVE-2020-25176

Rockwell Automation ISaGRAF5 Runtime Relative Path Traversal

Description

Some commands used by the Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x eXchange Layer (IXL) protocol perform various file operations in the file system. Since the parameter pointing to the file name is not checked for reserved characters, it is possible for a remote, unauthenticated attacker to traverse an application’s directory, which could lead to remote code execution.

Remediation

Solution:

  • Rockwell Automation recommends users update to ISaGRAF Runtime 5 Version 5.72.00. End users are encouraged to restrict or block access on TCP 1131 and TCP 1132 from outside the industrial control system. Confirm the least-privilege user principle is followed and user/service account access to Runtime's folder location is granted with a minimum amount of rights needed. Rockwell Automation recommends users of affected versions evaluate the mitigations provided and apply the appropriate mitigations to deployed products. Users are encouraged to combine this guidance with the general security guidelines for a comprehensive defense-in-depth strategy. To reduce risk, Rockwell Automation recommends users: Employ proper network segmentation and security controls. Minimize network exposure for all control system devices. Locate control systems behind firewalls. Isolate control systems from other networks when possible. Refer to the Converged Plantwide Ethernet (CPwE) Design and Implementation Guide for best practices deploying network segmentation and broader defense-in-depth strategies. Consider using proper network infrastructure controls, such as firewalls, UTM devices, VPN, or other security appliances. Ensure the least-privilege user principle is followed, and user/service account access to Runtime’s folder location is granted with a minimum amount of rights, as needed. Please see publications from Rockwell Automation and Schneider Electric, Xylem, or contact GE for further information about how to mitigate these vulnerabilities in additional affected products.

Categories

9.1
CVSS
Severity: Critical
CVSS 3.1 •
CVSS 2.0 •
EPSS 2.61% Top 20%
Vendor Advisory schneider-electric.com
Affected: Rockwell Automation ISaGRAF Runtime
Published at:
Updated at:

References

Frequently Asked Questions

What is the severity of CVE-2020-25176?
CVE-2020-25176 has been scored as a critical severity vulnerability.
How to fix CVE-2020-25176?
To fix CVE-2020-25176: Rockwell Automation recommends users update to ISaGRAF Runtime 5 Version 5.72.00. End users are encouraged to restrict or block access on TCP 1131 and TCP 1132 from outside the industrial control system. Confirm the least-privilege user principle is followed and user/service account access to Runtime's folder location is granted with a minimum amount of rights needed. Rockwell Automation recommends users of affected versions evaluate the mitigations provided and apply the appropriate mitigations to deployed products. Users are encouraged to combine this guidance with the general security guidelines for a comprehensive defense-in-depth strategy. To reduce risk, Rockwell Automation recommends users: Employ proper network segmentation and security controls. Minimize network exposure for all control system devices. Locate control systems behind firewalls. Isolate control systems from other networks when possible. Refer to the Converged Plantwide Ethernet (CPwE) Design and Implementation Guide for best practices deploying network segmentation and broader defense-in-depth strategies. Consider using proper network infrastructure controls, such as firewalls, UTM devices, VPN, or other security appliances. Ensure the least-privilege user principle is followed, and user/service account access to Runtime’s folder location is granted with a minimum amount of rights, as needed. Please see publications from Rockwell Automation and Schneider Electric, Xylem, or contact GE for further information about how to mitigate these vulnerabilities in additional affected products.
Is CVE-2020-25176 being actively exploited in the wild?
It is possible that CVE-2020-25176 is being exploited or will be exploited in a near future based on public information. According to its EPSS score, there is a ~3% probability that this vulnerability will be exploited by malicious actors in the next 30 days.
What software or system is affected by CVE-2020-25176?
CVE-2020-25176 affects Rockwell Automation ISaGRAF Runtime.
This platform uses data from the NIST NVD, MITRE CVE, MITRE CWE, First.org and CISA KEV but is not endorsed or certified by these entities. CVE is a registred trademark of the MITRE Corporation and the authoritative source of CVE content is MITRE's CVE web site. CWE is a registred trademark of the MITRE Corporation and the authoritative source of CWE content is MITRE's CWE web site.