CVE-2025-24481

FactoryTalk® View Site Edition - Incorrect Permission Assignment

Description

An Incorrect Permission Assignment Vulnerability exists in the product and version listed above. The vulnerability is due to incorrect permissions being assigned to the remote debugger port and can allow for unauthenticated access to the system configuration.

Remediation

Solution:

  • Upgrade to V15 or apply patch, answer ID 1152306.

Workaround:

  • Protect physical access to the workstation & restrict access to port 8091 at the network or workstation.

Category

7.0
CVSS
Severity: High
CVSS 4.0 •
EPSS 0.01%
Affected: Rockwell Automation FactoryTalk® View Site Edition
Published at:
Updated at:

References

Frequently Asked Questions

What is the severity of CVE-2025-24481?
CVE-2025-24481 has been scored as a high severity vulnerability.
How to fix CVE-2025-24481?
To fix CVE-2025-24481: Upgrade to V15 or apply patch, answer ID 1152306.
Is CVE-2025-24481 being actively exploited in the wild?
As for now, there are no information to confirm that CVE-2025-24481 is being actively exploited. According to its EPSS score, there is a ~0% probability that this vulnerability will be exploited by malicious actors in the next 30 days.
What software or system is affected by CVE-2025-24481?
CVE-2025-24481 affects Rockwell Automation FactoryTalk® View Site Edition.
This platform uses data from the NIST NVD, MITRE CVE, MITRE CWE, First.org and CISA KEV but is not endorsed or certified by these entities. CVE is a registred trademark of the MITRE Corporation and the authoritative source of CVE content is MITRE's CVE web site. CWE is a registred trademark of the MITRE Corporation and the authoritative source of CWE content is MITRE's CWE web site.